Skip to content
LexBuild

30 CFR § 75.524 - Electric face equipment; electric equipment used in return air outby the last open crosscut; maximum level of alternating or direct electric current between frames of equipment.

---
identifier: "/us/cfr/t30/s75.524"
source: "ecfr"
legal_status: "authoritative_unofficial"
title: "30 CFR § 75.524 - Electric face equipment; electric equipment used in return air outby the last open crosscut; maximum level of alternating or direct electric current between frames of equipment."
title_number: 30
title_name: "Mineral Resources"
section_number: "75.524"
section_name: "Electric face equipment; electric equipment used in return air outby the last open crosscut; maximum level of alternating or direct electric current between frames of equipment."
chapter_name: "MINE SAFETY AND HEALTH ADMINISTRATION, DEPARTMENT OF LABOR"
subchapter_number: "O"
subchapter_name: "COAL MINE SAFETY AND HEALTH"
part_number: "75"
part_name: "MANDATORY SAFETY STANDARDS—UNDERGROUND COAL MINES"
positive_law: false
currency: "2026-03-24"
last_updated: "2026-03-24"
format_version: "1.1.0"
generator: "[email protected]"
authority: "30 U.S.C. 811, 813(h), 957."
regulatory_source: "35 FR 17890, Nov. 20, 1970, unless otherwise noted."
cfr_part: "75"
---

# 75.524 Electric face equipment; electric equipment used in return air outby the last open crosscut; maximum level of alternating or direct electric current between frames of equipment.

The maximum level of alternating or direct electric current that exists between the frames of any two units of electric face equipment that come in contact with each other in the working places of a coal mine, or between the frames of any two units of electric equipment that come in contact with each other in return air outby the last open crosscut, shall not exceed one ampere as determined from the voltage measured across a 0.1 ohm resistor connected between the frames of such equipment.

[38 FR 29998, Oct. 31, 1973]