Skip to content
LexBuild

30 CFR § 77.1103 - Flammable liquids; storage.

---
identifier: "/us/cfr/t30/s77.1103"
source: "ecfr"
legal_status: "authoritative_unofficial"
title: "30 CFR § 77.1103 - Flammable liquids; storage."
title_number: 30
title_name: "Mineral Resources"
section_number: "77.1103"
section_name: "Flammable liquids; storage."
chapter_name: "MINE SAFETY AND HEALTH ADMINISTRATION, DEPARTMENT OF LABOR"
subchapter_number: "O"
subchapter_name: "COAL MINE SAFETY AND HEALTH"
part_number: "77"
part_name: "MANDATORY SAFETY STANDARDS, SURFACE COAL MINES AND SURFACE WORK AREAS OF UNDERGROUND COAL MINES"
positive_law: false
currency: "2026-03-24"
last_updated: "2026-03-24"
format_version: "1.1.0"
generator: "[email protected]"
authority: "30 U.S.C. 811."
regulatory_source: "36 FR 9364, May 22, 1971, unless otherwise noted."
cfr_part: "77"
---

# 77.1103 Flammable liquids; storage.

(a) Flammable liquids shall be stored in accordance with standards of the National Fire Protection Association. Small quantities of flammable liquids drawn from storage shall be kept in properly identified safety cans.

(b) Unburied flammable-liquid storage tanks shall be mounted securely on firm foundations. Outlet piping shall be provided with flexible connections or other special fittings to prevent adverse effects from tank settling.

(c) Fuel lines shall be equipped with valves to cut off fuel at the source and shall be located and maintained to minimize fire hazards.

(d) Areas surrounding flammable-liquid storage tanks and electric substations and transformers shall be kept free from grass (dry), weeds, underbrush, and other combustible materials such as trash, rubbish, leaves and paper, for at least 25 feet in all directions.