Skip to content
LexBuild

30 CFR § 77.211-1 - Continuous methane monitoring device; installation and operation; automatic deenergization of electric equipment.

---
identifier: "/us/cfr/t30/s77.211-1"
source: "ecfr"
legal_status: "authoritative_unofficial"
title: "30 CFR § 77.211-1 - Continuous methane monitoring device; installation and operation; automatic deenergization of electric equipment."
title_number: 30
title_name: "Mineral Resources"
section_number: "77.211-1"
section_name: "Continuous methane monitoring device; installation and operation; automatic deenergization of electric equipment."
chapter_name: "MINE SAFETY AND HEALTH ADMINISTRATION, DEPARTMENT OF LABOR"
subchapter_number: "O"
subchapter_name: "COAL MINE SAFETY AND HEALTH"
part_number: "77"
part_name: "MANDATORY SAFETY STANDARDS, SURFACE COAL MINES AND SURFACE WORK AREAS OF UNDERGROUND COAL MINES"
positive_law: false
currency: "2026-03-24"
last_updated: "2026-03-24"
format_version: "1.1.0"
generator: "[email protected]"
authority: "30 U.S.C. 811."
regulatory_source: "36 FR 9364, May 22, 1971, unless otherwise noted."
cfr_part: "77"
---

# 77.211-1 Continuous methane monitoring device; installation and operation; automatic deenergization of electric equipment.

Continuous methane monitoring devices shall be set to deenergize automatically electric equipment when such monitor is not operating properly and to give a warning automatically when the concentration of methane reaches a maximum percentage determined by an authorized representative of the Secretary which shall not be more than 1.0 volume per centum of methane. An authorized representative of the Secretary shall require such monitor to deenergize automatically electric equipment when the concentration of methane reaches a maximum percentage determined by such representative which shall not be more than 2.0 volume per centum of methane.