Skip to content
LexBuild

33 CFR § 149.408 - What are the maintenance requirements for fire extinguishers?

---
identifier: "/us/cfr/t33/s149.408"
source: "ecfr"
legal_status: "authoritative_unofficial"
title: "33 CFR § 149.408 - What are the maintenance requirements for fire extinguishers?"
title_number: 33
title_name: "Navigation and Navigable Waters"
section_number: "149.408"
section_name: "What are the maintenance requirements for fire extinguishers?"
chapter_name: "COAST GUARD, DEPARTMENT OF HOMELAND SECURITY"
subchapter_number: "NN"
subchapter_name: "DEEPWATER PORTS"
part_number: "149"
part_name: "DEEPWATER PORTS: DESIGN, CONSTRUCTION, AND EQUIPMENT"
positive_law: false
currency: "2026-03-24"
last_updated: "2026-03-24"
format_version: "1.1.0"
generator: "[email protected]"
authority: "33 U.S.C. 1504, 1509; DHS Delegation No. 00170.1, Revision No. 01.4."
regulatory_source: "USCG-1998-3884, 71 FR 57651, Sept. 29, 2006, unless otherwise noted."
cfr_part: "149"
---

# 149.408 What are the maintenance requirements for fire extinguishers?

(a) Portable and semi-portable extinguishers must be inspected and maintained in accordance with NFPA 10 (incorporated by reference, see § 149.3).

(b) Certification or licensing by a state or local jurisdiction as a fire extinguisher servicing agency will be accepted by the Coast Guard as meeting the personnel certification requirements of NFPA 10 for annual maintenance and recharging of extinguishers.

(c) Monthly inspections required by NFPA 10 may be conducted by the owner, operator, person-in-charge, or a designated member of the crew.

(d) Non-rechargeable or non-refillable extinguishers must be inspected and maintained in accordance with NFPA 10; however, the annual maintenance need not be conducted by a certified person and can be conducted by the owner, operator, person-in-charge, or a designated member of the crew.

(e) The owner or managing operator must provide satisfactory evidence of the required servicing to the marine inspector. If any of the equipment or records has not been properly maintained, a qualified servicing facility must perform the required inspections, maintenance procedures, and hydrostatic pressure tests. A tag issued by a qualified servicing organization, and attached to each extinguisher, may be accepted as evidence that the necessary maintenance procedures have been conducted.

[USCG-2012-0196, 81 FR 48244, July 22, 2016]