Skip to content
LexBuild

40 CFR § 264.1032 - Standards: Process vents.

---
identifier: "/us/cfr/t40/s264.1032"
source: "ecfr"
legal_status: "authoritative_unofficial"
title: "40 CFR § 264.1032 - Standards: Process vents."
title_number: 40
title_name: "Protection of Environment"
section_number: "264.1032"
section_name: "Standards: Process vents."
chapter_name: "ENVIRONMENTAL PROTECTION AGENCY"
subchapter_number: "I"
subchapter_name: "SOLID WASTES"
part_number: "264"
part_name: "STANDARDS FOR OWNERS AND OPERATORS OF HAZARDOUS WASTE TREATMENT, STORAGE, AND DISPOSAL FACILITIES"
positive_law: false
currency: "2026-03-24"
last_updated: "2026-03-24"
format_version: "1.1.0"
generator: "[email protected]"
authority: "42 U.S.C. 6905, 6912(a), 6924, 6925, and 6939g."
regulatory_source: "45 FR 33221, May 19, 1980, unless otherwise noted."
cfr_part: "264"
---

# 264.1032 Standards: Process vents.

(a) The owner or operator of a facility with process vents associated with distillation, fractionation, thin-film evaporation, solvent extraction, or air or steam stripping operations managing hazardous wastes with organic concentrations of at least 10 ppmw shall either:

(1) Reduce total organic emissions from all affected process vents at the facility below 1.4 kg/h (3 lb/h) and 2.8 Mg/yr (3.1 tons/yr), or

(2) Reduce, by use of a control device, total organic emissions from all affected process vents at the facility by 95 weight percent.

(b) If the owner or operator installs a closed-vent system and control device to comply with the provisions of paragraph (a) of this section the closed-vent system and control device must meet the requirements of § 264.1033.

(c) Determinations of vent emissions and emission reductions or total organic compound concentrations achieved by add-on control devices may be based on engineering calculations or performance tests. If performance tests are used to determine vent emissions, emission reductions, or total organic compound concentrations achieved by add-on control devices, the performance tests must conform with the requirements of § 264.1034(c).

(d) When an owner or operator and the Regional Administrator do not agree on determinations of vent emissions and/or emission reductions or total organic compound concentrations achieved by add-on control devices based on engineering calculations, the procedures in § 264.1034(c) shall be used to resolve the disagreement.