Skip to content
LexBuild

46 CFR § 111.05-23 - Location of ground indicators.

---
identifier: "/us/cfr/t46/s111.05-23"
source: "ecfr"
legal_status: "authoritative_unofficial"
title: "46 CFR § 111.05-23 - Location of ground indicators."
title_number: 46
title_name: "Shipping"
section_number: "111.05-23"
section_name: "Location of ground indicators."
chapter_name: "COAST GUARD, DEPARTMENT OF HOMELAND SECURITY"
subchapter_number: "J"
subchapter_name: "ELECTRICAL ENGINEERING"
part_number: "111"
part_name: "ELECTRIC SYSTEMS—GENERAL REQUIREMENTS"
positive_law: false
currency: "2026-04-05"
last_updated: "2026-04-05"
format_version: "1.1.0"
generator: "[email protected]"
authority: "46 U.S.C. 3306, 3703; DHS Delegation No. 00170.1, Revision No. 01.2. Section 111.05-20 and Subpart 111.106 also issued under sec. 617, Pub. L. 111-281, 124 Stat. 2905."
regulatory_source: "CGD 74-125A, 47 FR 15236, Apr. 8, 1982, unless otherwise noted."
cfr_part: "111"
---

# 111.05-23 Location of ground indicators.

Ground indicators must:

(a) Be at the vessel's ship's service generator distribution switchboard for the normal power, normal lighting, and emergency lighting systems;

(b) Be at the propulsion switchboard for propulsion systems; and

(c) Be readily accessible.

(d) Be provided (at the distribution switchboard or at another location, such as a centralized monitoring position for the circuit affected) for each feeder circuit that is isolated from the main source by a transformer or other device.

An alarm contact or indicating device returned to the main switchboard via a control cable, that allows the detecting equipment to remain near the transformer or other isolating device for local troubleshooting, is allowed.

[CGD 74-125A, 47 FR 15236, Apr. 8, 1982, as amended by CGD 94-108, 61 FR 28276, June 4, 1996; 62 FR 23907, May 1, 1997]