Skip to content
LexBuild

46 CFR § 111.05-29 - Dual voltage direct current systems.

---
identifier: "/us/cfr/t46/s111.05-29"
source: "ecfr"
legal_status: "authoritative_unofficial"
title: "46 CFR § 111.05-29 - Dual voltage direct current systems."
title_number: 46
title_name: "Shipping"
section_number: "111.05-29"
section_name: "Dual voltage direct current systems."
chapter_name: "COAST GUARD, DEPARTMENT OF HOMELAND SECURITY"
subchapter_number: "J"
subchapter_name: "ELECTRICAL ENGINEERING"
part_number: "111"
part_name: "ELECTRIC SYSTEMS—GENERAL REQUIREMENTS"
positive_law: false
currency: "2026-04-05"
last_updated: "2026-04-05"
format_version: "1.1.0"
generator: "[email protected]"
authority: "46 U.S.C. 3306, 3703; DHS Delegation No. 00170.1, Revision No. 01.2. Section 111.05-20 and Subpart 111.106 also issued under sec. 617, Pub. L. 111-281, 124 Stat. 2905."
regulatory_source: "CGD 74-125A, 47 FR 15236, Apr. 8, 1982, unless otherwise noted."
cfr_part: "111"
---

# 111.05-29 Dual voltage direct current systems.

Each dual voltage direct current system must have a suitably sensitive ground detection system which indicates current in the ground connection, has a range of at least 150 percent of neutral current rating and indicates the polarity of the fault.

[CGD 94-108, 61 FR 28276, June 4, 1996]

****Grounded Conductors