46 CFR § 111.30-19 - Buses and wiring.

---
identifier: "/us/cfr/t46/s111.30-19"
source: "ecfr"
legal_status: "authoritative_unofficial"
title: "46 CFR § 111.30-19 - Buses and wiring."
title_number: 46
title_name: "Shipping"
section_number: "111.30-19"
section_name: "Buses and wiring."
chapter_name: "COAST GUARD, DEPARTMENT OF HOMELAND SECURITY"
subchapter_number: "J"
subchapter_name: "ELECTRICAL ENGINEERING"
part_number: "111"
part_name: "ELECTRIC SYSTEMS—GENERAL REQUIREMENTS"
positive_law: false
currency: "2026-04-05"
last_updated: "2026-04-05"
format_version: "1.1.0"
generator: "[email protected]"
authority: "46 U.S.C. 3306, 3703; DHS Delegation No. 00170.1, Revision No. 01.2. Section 111.05-20 and Subpart 111.106 also issued under sec. 617, Pub. L. 111-281, 124 Stat. 2905."
regulatory_source: "CGD 74-125A, 47 FR 15236, Apr. 8, 1982, unless otherwise noted."
cfr_part: "111"
---

# 111.30-19 Buses and wiring.

(a) *General.* Each bus must meet the requirements of either—

(1) Section 5.10 of IEEE 45.7-2012 (incorporated by reference; see § 110.10-1 of this subchapter); or

(2) IEC 60092-302:1997 (clause 7) (incorporated by reference; see § 110.10-1 of this subchapter).

(b) *Wiring.* Instrumentation and control wiring must be—

(1) Suitable for installation within in a switchboard enclosure and be rated at 90 °C or higher;

(2) Stranded copper;

(3) No. 14 AWG (2.10 mm
<sup>2</sup>) or larger or must be ribbon cable or similar conductor size cable recommended for use in low-power instrumentation, monitoring, or control circuits by the equipment manufacturer;

(4) Flame-retardant meeting test VW-1 of ANSI/UL 2556 or IEC 60332-1-1:2015 and IEC 60332-1-2:2015 (all incorporated by reference; see § 110.10-1 of this subchapter); and

(5) Extra flexible, if used on a hinged panel.

[CGD 94-108, 61 FR 28278, June 4, 1996, as amended at 62 FR 23908, May 1, 1997; USCG-2003-16630, 73 FR 65197, Oct. 31, 2008; USCG-2013-0671, 78 FR 60153, Sept. 30, 2013; USCG-2020-0075, 88 FR 16361, Mar. 16, 2023]