Skip to content
LexBuild

46 CFR § 111.60-1 - Construction and testing of cable.

---
identifier: "/us/cfr/t46/s111.60-1"
source: "ecfr"
legal_status: "authoritative_unofficial"
title: "46 CFR § 111.60-1 - Construction and testing of cable."
title_number: 46
title_name: "Shipping"
section_number: "111.60-1"
section_name: "Construction and testing of cable."
chapter_name: "COAST GUARD, DEPARTMENT OF HOMELAND SECURITY"
subchapter_number: "J"
subchapter_name: "ELECTRICAL ENGINEERING"
part_number: "111"
part_name: "ELECTRIC SYSTEMS—GENERAL REQUIREMENTS"
positive_law: false
currency: "2026-04-05"
last_updated: "2026-04-05"
format_version: "1.1.0"
generator: "[email protected]"
authority: "46 U.S.C. 3306, 3703; DHS Delegation No. 00170.1, Revision No. 01.2. Section 111.05-20 and Subpart 111.106 also issued under sec. 617, Pub. L. 111-281, 124 Stat. 2905."
regulatory_source: "CGD 74-125A, 47 FR 15236, Apr. 8, 1982, unless otherwise noted."
cfr_part: "111"
---

# 111.60-1 Construction and testing of cable.

(a) Electric cables constructed of stranded copper conductors, thermoplastic, elastomeric or other insulation, moisture-resistant jackets, and, where applicable, armoring and outer-sheathing must meet all the requirements of IEC 60092-350:2014, 60092-352:2005, 60092-353:2016, 60092-354:2014, 60092-360:2014, IEC/TR 60092-370:2009, 60092-376:2017, IEEE 1580, ANSI/UL 1072, ANSI/UL 1309, or MIL-DTL-24640C or MIL-DTL-24643C (all incorporated by reference; see § 110.10-1 of this subchapter), including the respective flammability tests contained therein.

(b) IEC 60092 series cable must meet the Category A or A F/R flammability requirements of IEC 60332-3-22:2009 or 60332-3-21:2000 (both incorporated by reference; see § 110.10-1 of this subchapter).

[USCG-2020-0075, 88 FR 16363, Mar. 16, 2023]