46 CFR § 161.002-6 - Testing requirements.

---
identifier: "/us/cfr/t46/s161.002-6"
source: "ecfr"
legal_status: "authoritative_unofficial"
title: "46 CFR § 161.002-6 - Testing requirements."
title_number: 46
title_name: "Shipping"
section_number: "161.002-6"
section_name: "Testing requirements."
chapter_name: "COAST GUARD, DEPARTMENT OF HOMELAND SECURITY"
subchapter_number: "Q"
subchapter_name: "EQUIPMENT, CONSTRUCTION, AND MATERIALS: SPECIFICATIONS AND APPROVAL"
part_number: "161"
part_name: "ELECTRICAL EQUIPMENT"
positive_law: false
currency: "2026-03-24"
last_updated: "2026-03-24"
format_version: "1.1.0"
generator: "[email protected]"
authority: "46 U.S.C. 3306, 3703, 4302; E.O. 12234, 45 FR 58801, 3 CFR, 1980 Comp., p. 277; DHS Delegation 00170.1, Revision No. 01.4."
cfr_part: "161"
---

# 161.002-6 Testing requirements.

(a) Devices must be tested and listed for fire service by an accepted independent laboratory, as accepted in accordance with § 159.010 of this subchapter, or by a NRTL as set forth in 29 CFR 1910.7.

(b) Each fire detection device must comply with the following standards (incorporated by reference, see § 161.002-1) as appropriate:

(1) Control units—UL 864;

(2) Heat detectors—UL 521;

(3) Smoke detectors—UL 268;

(4) Flame detectors—ANSI/FM 3260;

(5) Audible alarms—UL 464 or UL 1480;

(6) Visual alarms—UL 1971; and

(7) Manual Signaling Boxes—UL 38.

(c) All devices must be tested by an accepted independent laboratory, as defined in § 159.010 of this subchapter, to meet the marine environment testing requirements in Table 161.002-6(c) of this section. The test parameters are found in IEC 60092-504 (incorporated by reference, see § 161.002-1).

Table 161.002-6(**c**)—Marine Environmental Testing Requirements

| IEC 60092-504 Environmental type test | Category 1 | Category 2 | Category 3 |
| --- | --- | --- | --- |
| 1—Visual inspection | X | X | X |
| 2—Functional test | X | X | X |
| 3—High voltage test | X | X | X |
| 4a—Power supply variations | X | X | X |
| 4b—Power supply failure | X | X | X |
| 5—Insulation resistance | X | X | X |
| 6—Cold with gradual temp. change | X (5 °C) | X (−25 °C) | X (5 °C) |
| 7—Dry heat with gradual temp. change | X (55 °C) | X (55 °C) | X (55 °C) |
| 8—Damp heat, cyclic | X | X | X |
| 9—Salt mist |  | X |  |
| 10—Vibration (sinusoidal) | X | X | X |
| 11b—Inclination, dynamic | X | X | X |
| 13—Electrostatic discharge | X | X | X |
| 14—Electromagnetic field | X | X | X |
| 15—Conducted low frequency | X | X | X |
| 16(a)—Conducted radio frequency (3 V rms) | X |  |  |
| 16(b)—Conducted radio frequency (10 V rms) |  | X | X |
| 17—Burst/fast transients | X | X | X |
| 18—Surge/slow transients | X | X | X |
| 19(a)—Radiated emission (general power) | X |  |  |
| 19(b)—Radiated emission (bridge and deck zone) |  | X | X |
| 20(a)—Conducted emission (general power) | X |  |  |
| 20(b)—Conducted emission (bridge and deck zone) |  | X | X |
| This test only needs to be completed if the device is in a location with moving mechanical parts. |  |  |  |

(d) All fire detection system control units and remote annunciators must have enclosure protection as outlined in part 5 of IEC 60092-504 (incorporated by reference, see § 161.002-1) if the requirements exceed those of 46 CFR 111.01-9. Otherwise, 46 CFR 111.01-9 must be complied with.

[USCG-2012-0196, 81 FR 48275, July 22, 2016]