46 CFR § 169.559 - Fire pumps.

---
identifier: "/us/cfr/t46/s169.559"
source: "ecfr"
legal_status: "authoritative_unofficial"
title: "46 CFR § 169.559 - Fire pumps."
title_number: 46
title_name: "Shipping"
section_number: "169.559"
section_name: "Fire pumps."
chapter_name: "COAST GUARD, DEPARTMENT OF HOMELAND SECURITY"
subchapter_number: "R"
subchapter_name: "NAUTICAL SCHOOLS"
part_number: "169"
part_name: "SAILING SCHOOL VESSELS"
positive_law: false
currency: "2026-03-24"
last_updated: "2026-03-24"
format_version: "1.1.0"
generator: "[email protected]"
authority: "33 U.S.C. 1321(j); 46 U.S.C. 3306, 6101; Pub. L. 103-206, 107 Stat. 2439; E.O. 11735, 38 FR 21243, 3 CFR, 1971-1975 Comp., p. 793; DHS Delegation 00170.1, Revision No. 01.4; § 169.117 also issued under the authority of 44 U.S.C. 3507."
regulatory_source: "CGD 83-005, 51 FR 896, Jan. 9, 1986, unless otherwise noted."
cfr_part: "169"
---

# 169.559 Fire pumps.

(a) Each sailing school vessel must be equipped with fire pumps as required in Table 169.559(a).

Table 169.559(**a**)—Fire Pumps

| Length | Exposed and partially protected water service | Protected water service |
| --- | --- | --- |
| 65 feet but less than 90 feet | 1 | 0 |
| 90 feet but less than 120 feet | 1 | 1 |
| 120 feet or greater | 2 | 1 |
| May be driven off a propulsion engine and may be used as a bilge pump. |  |  |
| Must be driven by a source of power independent of the propulsion engine and may be used as a bilge pump. |  |  |
| One pump may be driven off a propulsion unit and one pump may be used as a bilge pump. Pumps must be located in separate spaces. |  |  |

(b) Fire pump capacity must be in accordance with the following:

| Vessel length | Minimum capacity |
| --- | --- |
| Less than 90 ft | 5.5 m/hr (25 gpm). |
| 90 feet but less than 120 ft | 11.0 m/hr (50 gpm). |
| Greater than 120 ft | 14.3 m/hr (66.6 gpm). |

(c) Each fire pump must be fitted with a pressure gage on the discharge side of the pump.

(d) Each vessel must have a hand operated portable fire pump having a capacity of at least 1.1 m
<sup>3</sup>/hr (5 gpm). This pump must be equipped with suction and discharge hose suitable for use in firefighting.