Skip to content
LexBuild

46 CFR § 181.420 - Pre-engineered fixed gas fire extinguishing systems.

---
identifier: "/us/cfr/t46/s181.420"
source: "ecfr"
legal_status: "authoritative_unofficial"
title: "46 CFR § 181.420 - Pre-engineered fixed gas fire extinguishing systems."
title_number: 46
title_name: "Shipping"
section_number: "181.420"
section_name: "Pre-engineered fixed gas fire extinguishing systems."
chapter_name: "COAST GUARD, DEPARTMENT OF HOMELAND SECURITY"
subchapter_number: "T"
subchapter_name: "SMALL PASSENGER VESSELS (UNDER 100 GROSS TONS)"
part_number: "181"
part_name: "FIRE PROTECTION EQUIPMENT"
positive_law: false
currency: "2026-04-05"
last_updated: "2026-04-05"
format_version: "1.1.0"
generator: "[email protected]"
authority: "46 U.S.C. 2103, 3306; E.O. 12234, 45 FR 58801, 3 CFR, 1980 Comp., p. 277; DHS Delegation 00170.1, Revision No. 01.4."
regulatory_source: "CGD 85-080, 61 FR 982, Jan. 10, 1996, unless otherwise noted."
cfr_part: "181"
---

# 181.420 Pre-engineered fixed gas fire extinguishing systems.

(a) A pre-engineered fixed gas fire extinguishing system must:

(1) Be approved by the Commandant;

(2) Be capable of manual actuation from outside the space in addition to automatic actuation by a heat detector;

(3) Automatically shut down all power ventilation systems and all engines that draw intake air from within the protected space; and

(4) Be installed in accordance with the manufacturer's instructions.

(b) A vessel on which a pre-engineered fixed gas fire extinguishing system is installed must have the following equipment at the operating station:

(1) A light to indicate discharge;

(2) An audible alarm that sounds upon discharge; and

(3) A means to reset devices used to automatically shut down ventilation systems and engines as required by paragraph (a)(3) of this section.

(c) Only one pre-engineered fixed gas fire extinguishing system is allowed to be installed in each space protected by such a system.