Skip to content
LexBuild

49 CFR § 192.169 - Compressor stations: Pressure limiting devices.

---
identifier: "/us/cfr/t49/s192.169"
source: "ecfr"
legal_status: "authoritative_unofficial"
title: "49 CFR § 192.169 - Compressor stations: Pressure limiting devices."
title_number: 49
title_name: "Transportation"
section_number: "192.169"
section_name: "Compressor stations: Pressure limiting devices."
chapter_name: "PIPELINE AND HAZARDOUS MATERIALS SAFETY ADMINISTRATION, DEPARTMENT OF TRANSPORTATION"
subchapter_number: "D"
subchapter_name: "PIPELINE SAFETY"
part_number: "192"
part_name: "TRANSPORTATION OF NATURAL AND OTHER GAS BY PIPELINE: MINIMUM FEDERAL SAFETY STANDARDS"
positive_law: false
currency: "2026-04-05"
last_updated: "2026-04-05"
format_version: "1.1.0"
generator: "[email protected]"
authority: "30 U.S.C. 185(w)(3), 49 U.S.C. 5103, 60101  and 49 CFR 1.97."
regulatory_source: "35 FR 13257, Aug. 19, 1970, unless otherwise noted."
cfr_part: "192"
---

# 192.169 Compressor stations: Pressure limiting devices.

(a) Each compressor station must have pressure relief or other suitable protective devices of sufficient capacity and sensitivity to ensure that the maximum allowable operating pressure of the station piping and equipment is not exceeded by more than 10 percent.

(b) Each vent line that exhausts gas from the pressure relief valves of a compressor station must extend to a location where the gas may be discharged without hazard.