Skip to content
LexBuild

49 CFR § 193.2101 - Scope.

---
identifier: "/us/cfr/t49/s193.2101"
source: "ecfr"
legal_status: "authoritative_unofficial"
title: "49 CFR § 193.2101 - Scope."
title_number: 49
title_name: "Transportation"
section_number: "193.2101"
section_name: "Scope."
chapter_name: "PIPELINE AND HAZARDOUS MATERIALS SAFETY ADMINISTRATION, DEPARTMENT OF TRANSPORTATION"
subchapter_number: "D"
subchapter_name: "PIPELINE SAFETY"
part_number: "193"
part_name: "LIQUEFIED NATURAL GAS FACILITIES: FEDERAL SAFETY STANDARDS"
positive_law: false
currency: "2026-03-24"
last_updated: "2026-03-24"
format_version: "1.1.0"
generator: "[email protected]"
authority: "49 U.S.C. 5103, 60102, 60103, 60104, 60108, 60109, 60110, 60113, 60118; and 49 CFR 1.53."
regulatory_source: "45 FR 9203, Feb. 11, 1980, unless otherwise noted."
cfr_part: "193"
---

# 193.2101 Scope.

(a) Each LNG facility designed after March 31, 2000 must comply with the requirements of this part and of NFPA-59A-2001 (incorporated by reference, *see* § 193.2013). If there is a conflict between this Part and NFPA-59A-2001, the requirements in this part prevail.

(b) Each stationary LNG storage tank must comply with Section 7.2.2 of NFPA-59A-2006 (incorporated by reference, *see* § 193.2013) for seismic design of field fabricated tanks. All other LNG storage tanks must comply with API Std-620 (incorporated by reference, *see* § 193.2013) for seismic design.