Energy Conservation Program: Energy Conservation Standards for Uninterruptible Power Supplies
---
identifier: "/us/fr/C1-2019-26354"
source: "fr"
legal_status: "authoritative_unofficial"
title: "Energy Conservation Program: Energy Conservation Standards for Uninterruptible Power Supplies"
title_number: 0
title_name: "Federal Register"
section_number: "C1-2019-26354"
section_name: "Energy Conservation Program: Energy Conservation Standards for Uninterruptible Power Supplies"
positive_law: false
currency: "2020-01-21"
last_updated: "2020-01-21"
format_version: "1.1.0"
generator: "[email protected]"
agency: "Energy Department"
document_number: "C1-2019-26354"
document_type: "rule"
publication_date: "2020-01-21"
agencies:
- "Energy Department"
cfr_references:
- "10 CFR Part 430"
rin: "1904-AD69"
fr_citation: "85 FR 3232"
fr_volume: 85
docket_ids:
- "Docket Number EERE-2016-BT-STD-0022"
---
# [Corrected]
**Correction**
In rule document 2019-2635 beginning on page 1447 in the issue of Friday, January 10, 2020, make the following correction:
§ 430.32
On page 1503, in § 430.32(z)(3) the table should appear as follows:
| Battery charger product class | Rated output power | Minimum efficiency |
| --- | --- | --- |
| 10a (VFD UPSs) | 0
≤ 300 | −1.20E-06 *
+ 7.17E-04 *
+ 0.862. |
| | 300
≤ 700 | −7.85E-08 *
+ 1.01E-04 *
+ 0.946. |
| | > 700 | −7.23E-09 *
+ 7.52E-06 *
+ 0.977. |
| 10b (VI UPSs) | 0
≤ 300 | −1.20E-06 *
+ 7.19E-04 *
+ 0.863. |
| | 300
≤ 700 | −7.67E-08 *
+ 1.05E-04 *
+ 0.947. |
| | > 700 | −4.62E-09 *
+ 8.54E-06 *
+ 0.979. |
| 10c (VFI UPSs) | 0
≤ 300 | −3.13E-06 *
+ 1.96E-03 *
+ 0.543. |
| | 300
≤ 700 | −2.60E-07 *
+ 3.65E-04 *
+ 0.764. |
| | > 700 | −1.70E-08 *
+ 3.85E-05 *
+ 0.876. |