# Constellation Energy Generation, LLC; Arizona Public Service Company; Duke Energy Carolinas, LLC
**AGENCY:**
Nuclear Regulatory Commission.
**ACTION:**
Exemptions; issuance.
**SUMMARY:**
The U.S. Nuclear Regulatory Commission (NRC) issued four exemptions in response to requests from Arizona Public Service Company; Constellation Energy Generation, LLC; and Duke Energy Carolinas, LLC. The exemptions will allow the licensees to deviate from the requirements for the MAGNASTOR® storage cask system in Certificate of Compliance No. 1031, Amendment No. 7 and Amendment No. 9, by utilizing storage cask lids that were not fabricated in accordance with the requirements of two codes issued by the American Concrete Institute. The NRC is issuing a single notice to announce the issuance of these exemptions because these are nearly identical.
**DATES:**
The two exemptions to Arizona Public Service Company; Constellation Energy Generation, LLC were issued on May 13, 2022, and two exemptions were issued to Duke Energy Carolinas, LLC on May 16, 2022.
**ADDRESSES:**
Please refer to Docket ID NRC-2022-0113 when contacting the NRC about the availability of information regarding this document. You may obtain publicly available information related to this document using any of the following methods:
• *Federal Rulemaking website:* Go to *https://www.regulations.gov* and search for Docket ID NRC-2022-0113. Address questions about Dockets IDs in *Regulations.gov* to Stacy Schumann; telephone: 301-415-0624; email: *[email protected].* For technical questions, contact the individual listed in the *For Further Information Contact* section of this document.
• *NRC's Agencywide Documents Access and Management System (ADAMS):* You may obtain publicly available documents online in the ADAMS Public Documents collection at *https://www.nrc.gov/reading-rm/adams.html.* To begin the search, select “Begin Web-based ADAMS Search.” For problems with ADAMS, please contact the NRC's Public Document Room (PDR) reference staff at 1-800-397-4209, 301-415-4737, or by email to *[email protected].* For the convenience of the reader, instructions about obtaining materials referenced in this document are provided in the “Availability of Documents” section.
• *NRC's PDR:* You may examine and purchase copies of public documents, by appointment, at the NRC's PDR, Room P1 B35, One White Flint North, 11555 Rockville Pike, Rockville, Maryland 20852. To make an appointment to visit the PDR, please send an email to *[email protected]* or call 1-800-397-4209 or 301-415-4737, between 8:00 a.m. and 4:00 p.m. (ET), Monday through Friday, except Federal holidays.
**FOR FURTHER INFORMATION CONTACT:**
Bernard White, Office of Nuclear Material Safety and Safeguards, U.S. Nuclear Regulatory Commission, Washington, DC 20555-0001; telephone: 301-415-6577, email: *[email protected].*
**SUPPLEMENTARY INFORMATION:**
**I. Introduction**
The NRC issued four exemptions in response to requests dated March 31, 2022, and April 7, 2022, from Constellation Energy Generation, LLC and Arizona Public Service Company; and Duke Energy Carolinas, LLC, respectively. The exemptions allow exemption from the requirements of title 10 of the Code of Federal Regulations (10 CFR) sections 72.212(a)(2), 72.212(b)(3), 72.212(b)(5)(i), 72.214, and the portion of 10 CFR 72.212(b)(11) which requires compliance with the terms and conditions set forth in the certificate of compliance for each spent fuel cask used by an independent spent fuel storage installation general licensee.
The exemptions requested authorization to load, and store spent fuel in MAGNASTOR® storage casks with lids that were not fabricated in accordance with Technical Specification A4.2 as specified in Amendment Nos. 7 and 9 of the NAC International Certificate of Compliance No. 1031 for the MAGNASTOR® storage system. Amendment No. 7 is used at the Catawba, McGuire and Palo Verde independent spent fuel storage installations. Amendment No. 9 is used at the Three Mile Island, Unit I independent spent fuel storage installation.
Technical Specification, Appendix A, A4.2 requires the concrete cask to be designed and fabricated in accordance with the American Concrete Institute Specifications ACI-349, “Code Requirements for Nuclear Safety Related Concrete Structures,” and ACI-318, “Building Code Requirements for Structural Concrete,” which according to the technical specifications govern the concrete cask design and construction, respectively.
NAC submitted an amendment request to eliminate the need for compliance with the referenced technical specification for the concrete in the cask lids in the Certificate of Compliance No. 1031 for the MAGNASTOR® storage system, however the exemptions were necessary to meet loading campaigns scheduled before resolution of the NAC's amendment request. The applications provided information documenting that concrete in the cask lids is not relied upon for the strength safety function provided by the ACI codes in Technical Specification, Appendix A, A4.2, and the concrete in the cask lids was fabricated using standards that ensure the concrete will continue to meet the required shielding safety function. Based on the NRC staff's evaluation of the exemption requests, and the statements and representations provided by the applicants in the exemption requests, the staff concluded that the proposed actions to exempt the cask lids from the current Technical Specification in A4.2 at each of the ISFSI sites is authorized by law and will not endanger life, property, or the common defense and security, and is otherwise in the public interest and, therefore meets the exemption requirements in 10 CFR 72.7.
**II. Availability of Documents**
The following table provides the facility name, docket number, document description, and ADAMS accession numbers related to each exemption issued. For further details with respect to these exemptions, see the requests for exemption for each facility in ADAMS. For additional directions on accessing information in ADAMS see the *ADDRESSES* section of this document.
| Document description | ADAMS Accession No. |
| --- | --- |
| | |
| | |
| Palo Verde Nuclear Generating Station Units 1, 2, and 3 and Independent Spent Fuel Storage Installation Docket Nos. STN 50-528/529/530 and 72-44 Renewed Operating License Nos. NPF-41, NPF-51, NPF-74 Request for Exemption from NAC-MAGNASTOR Certificate of Compliance 72-1031—Cask Lid Design Requirements, dated March 31, 2022 | ML22090A098. |
| Palo Verde Nuclear Generating Station Units 1, 2, and 3 and Independent Spent Fuel Storage Installation Docket Nos. STN 50-528/529/530 and 72-44 Renewed Operating License Nos. NPF-41, NPF-51, NPF-74 Request for Exemption from NAC-MAGNASTOR Certificate of Compliance 72-1031—Cask Lid Design Requirements—Supplement, dated April 28, 2022 | ML22118B162. |
| Issuance of exemption for Palo Verde ISFSI | ML22111A282 (Package). |
| | |
| | |
| Request for an Exemption to the Requirements of Certificate of Compliance No. 1031 for the NAC MAGNASTOR® Storage System, dated March 31, 2022 | ML22090A182. |
| Supplemental Information to Exemption to the Requirements of Certificate of Compliance No. 1031 for the NAC MAGNASTOR® Storage System, dated April 26, 2022 | ML22116A236. |
| Issuance of exemption for TMI-1 ISFSI | ML22110A110 (Package). |
| | |
| | |
| Request for an Exemption to the Requirements of Certificate of Compliance No. 1031 for the NAC MAGNASTOR Storage System, dated April 7, 2022 | ML22097A057. |
| Supplement to the Request for an Exemption to the Requirements of Certificate of Compliance No. 1031 for the NAC MAGNASTOR Storage System, dated April 28, 2022 | ML22118B165. |
| Issuance of exemption for Catawba ISFSI | ML22111A356 (Package). |
| | |
| | |
| Request for an Exemption to the Requirements of Certificate of Compliance No. 1031 for the NAC MAGNASTOR Storage System, dated April 7, 2022 | ML22097A057. |
| Supplement to the Request for an Exemption to the Requirements of Certificate of Compliance No. 1031 for the NAC MAGNASTOR Storage System, dated April 28, 2022 | ML22118B165. |
| Issuance of exemption for McGuire ISFSI | ML22111A310 (Package). |
| | |
| Submission of an Amendment Request for the NAC International MAGNASTOR® Cask System Amendment No. 12, dated January 24, 2022 | ML22024A374. |
| Supplement to NAC's Amendment Request for the NAC International MAGNASTOR® Cask System Amendment No. 12, dated March 18, 2022 | ML22077A769. |
| RAI Response to NAC's Amendment Request for the NAC International MAGNASTOR® Cask System Amendment No. 12, dated April 18, 2022 | ML22108A197. |
The NRC may post additional materials related to this document, included public comments, on the Federal rulemaking website. In addition, the Federal rulemaking website allows members of the public to receive alerts when changes or additional occur in a docket folder. To subscribe: (1) navigate to the docket folder (NRC-2022-0113); (2) click the “Subscribe” link, and (3) enter your email address and click on “Subscribe” link.
For the Nuclear Regulatory Commission.
Dated: May 31, 2022.
Yoira K. Diaz-Sanabria,
Chief,Storage and Transportation Licensing Branch, Division of Fuel Management, Office of Nuclear Material Safety and Safeguards.