46 CFR § 108.423 - Fire hydrants and associated equipment.

---
identifier: "/us/cfr/t46/s108.423"
source: "ecfr"
legal_status: "authoritative_unofficial"
title: "46 CFR § 108.423 - Fire hydrants and associated equipment."
title_number: 46
title_name: "Shipping"
section_number: "108.423"
section_name: "Fire hydrants and associated equipment."
chapter_name: "COAST GUARD, DEPARTMENT OF HOMELAND SECURITY"
subchapter_number: "I-A"
subchapter_name: "A—MOBILE OFFSHORE DRILLING UNITS"
part_number: "108"
part_name: "DESIGN AND EQUIPMENT"
positive_law: false
currency: "2026-04-05"
last_updated: "2026-04-05"
format_version: "1.1.0"
generator: "[email protected]"
authority: "43 U.S.C. 1333; 46 U.S.C. 3102, 3306; DHS Delegation No. 00170.1, Revision No. 01.4."
regulatory_source: "CGD 73-251, 43 FR 56808, Dec. 4, 1978, unless otherwise noted."
cfr_part: "108"
---

# 108.423 Fire hydrants and associated equipment.

(a) A fire main system must have enough fire hydrants so that each accessible space may be sprayed with at least two spray patterns of water.

(b) In a main machinery space, except a shaft alley with no assigned space for stowage of combustibles, each spray pattern of water must be from one length of fire hose and each must be from a separate outlet. In all other spaces at least one spray pattern of water must be from one length of fire hose.

(c) No outlet on a fire hydrant may point above the horizontal.

(d) Each fire hydrant must have at least one spanner and at least one fire hose rack or reel.